Lennox LED Blink Codes

8 diagnostic blink codes documented

1 Flash (slow) info
No Previous Fault Stored

No diagnostic fault has been recorded. System is normal.

  1. No action needed
2 Flashes (slow) critical
System Lockout - Retries Exhausted

Maximum ignition retries exceeded. Furnace in lockout.

  1. Power cycle to reset
  2. Check gas supply
  3. Clean flame sensor
  4. Test igniter
3 Flashes (slow) high
Pressure Switch Fault

Pressure switch did not close or opened during operation.

  1. Inspect flue and intake pipes
  2. Check pressure hose for cracks
  3. Test pressure switch
  4. Measure inducer motor amps
4 Flashes (slow) high
High Limit Switch Open

High temperature limit switch has tripped.

  1. Replace air filter
  2. Check return and supply vents
  3. Test blower motor
  4. Check gas pressure
5 Flashes (slow) critical
Flame Sensed Without Gas Valve Call

Control board sees flame when gas valve is off.

  1. SAFETY: Turn off gas supply
  2. Test gas valve
  3. Inspect flame sensor circuit
6 Flashes (slow) medium
Low Voltage Power Fault

24V control circuit interruption detected.

  1. Check transformer output
  2. Tighten all wire connections
  3. Inspect thermostat wiring
7 Flashes (slow) high
Igniter Warm-Up Failure

Igniter did not reach ignition temperature in expected time.

  1. Test igniter resistance
  2. Check line voltage to board
  3. Test igniter output from board
8 Flashes (slow) high
Flame Lost During Run

Flame was established but lost during the heating cycle.

  1. Clean flame sensor
  2. Check gas pressure
  3. Test flame signal (should be 2+ microamps)
  4. Verify furnace ground